Calculate voltage drop, percentage drop and estimated load voltage for DC, single-phase AC and balanced three-phase AC circuits using cable length, conductor material, cross-section and power factor.
Example: a 230 V single-phase circuit carries 10 A through 30 m of one-way 2.5 mm² copper cable. What is the voltage drop?
For AC circuits: if cable-specific data is unavailable, 0.08 Ω/km is used as an approximate default reactance from the Schneider guide. At power factor 1, reactance does not affect the result.
Voltage drop5.688 V 2 × 10 A × 9.48 Ω/km × 0.03 km = 5.688 V
Voltage-drop percentage2.473043478260869565% Percentage = voltage drop ÷ source voltage × 100.
Estimated voltage at load224.312 V R ≈ 9.48 Ω/km
✓ Uses steady-load voltage-drop formulas and the conductor-resistance approximation published in the Schneider Electric Installation Guide
How is it calculated?For DC, ΔV = 2 × I × R × L. For single-phase AC, ΔV = 2 × I × (R cosφ + X sinφ) × L. For balanced three-phase AC, ΔV = √3 × I × (R cosφ + X sinφ) × L. L is one-way cable length in kilometres. Conductor resistance is estimated as R = 23.7 ÷ S for copper or R = 37.6 ÷ S for aluminium, with S in mm². This is an engineering estimate, not a substitute for cable-manufacturer data, electrical codes or qualified design.
This calculation runs in your browser. Your values are not sent to our server.
Single-phase AC: ΔV = 2 × I × (R cosφ + X sinφ) × L
Balanced three-phase: ΔV = √3 × I × (R cosφ + X sinφ) × L
Approximate copper resistance: R = 23.7 ÷ S Ω/km
Approximate aluminium resistance: R = 37.6 ÷ S Ω/km
Voltage-drop percentage = ΔV ÷ source voltage × 100
Estimated load voltage = source voltage − ΔV
How it works
Choose DC, single-phase AC, or balanced three-phase AC.
Enter source voltage, load current, one-way cable length, conductor material and conductor cross-section in square millimetres.
For AC circuits you can enter power factor and cable inductive reactance. If cable-specific X is unavailable, the interface starts with 0.08 Ω/km as the Schneider guide’s approximate default.
Conductor resistance is estimated as R = 23.7 ÷ S for copper or R = 37.6 ÷ S for aluminium, where R is in Ω/km and S is in mm².
Single-phase drop uses ΔV = 2 × I × (R cosφ + X sinφ) × L. Balanced three-phase uses √3 instead of 2. DC uses the resistive relationship ΔV = 2 × I × R × L.
The calculator reports voltage drop in volts, drop as a percentage of source voltage, and the arithmetic voltage remaining at the load.
This is a steady-load estimate. Manufacturer cable resistance/reactance, temperature, installation method and local electrical-code requirements can change the real design result.
Should I enter one-way cable length or round-trip length?
Enter one-way cable length. The calculator applies the two-conductor factor automatically for DC and single-phase circuits, and √3 for balanced three-phase circuits.
Can it calculate both copper and aluminium cable voltage drop?
Yes. It uses the Schneider guide’s simplified conductor-resistance approximation for copper or aluminium based on cross-sectional area.
What does power factor change?
For AC, power factor participates in the impedance voltage-drop term with conductor resistance and inductive reactance. At power factor 1, sinφ is zero and X has no effect.
What should I use for cable reactance X if I do not know it?
The calculator starts at 0.08 Ω/km, an approximate value given by the Schneider guide when no other information is available. Manufacturer-specific cable data is preferable.
Does this calculator select a code-compliant wire size?
No. It estimates voltage drop only. It does not verify ampacity, overcurrent protection, conductor temperature, installation method or local electrical-code requirements.
Why can a cable-manufacturer calculator give a different answer?
Manufacturer software may use cable-specific resistance at operating temperature and reactance for the exact cable construction and installation, which is more specific than this general estimate.